Local cover image
Local cover image
Image from Google Jackets

Development of heat transfer coefficient correlation for minichannel condenser

By: Contributor(s): Publication details: Prayagraj Pushpa Publishing House 2023Edition: Vol.33, JunDescription: 29-40pSubject(s): Online resources: In: JP journal of heat and mass transferSummary: Vapour compression refrigeration (VCR) system was designed, developed, and fabricated for testing alternative refrigerants such as R152a, R600a, R290 and mixture of R290/R600a (50/50% by mass) over presently used R134a with aluminium minichannel condenser. Heater bank was provided for controlling condensation and evaporator temperature along with sub-cooling and superheating temperature by using PID controllers. All the refrigerants are tested for condensation temperature ranging from 40°C to 55°C while evaporation temperature ranges from –15°C to 15°C. Refrigerant charge was reduced 50% with the minichannel condenser over the conventional condenser. Two phase condensation heat transfer coefficient correlation was developed from the experimental data points within ±15% with existing correlations.
Tags from this library: No tags from this library for this title. Log in to add tags.
Star ratings
    Average rating: 0.0 (0 votes)
Holdings
Item type Current library Status Barcode
Articles Abstract Database Articles Abstract Database School of Engineering & Technology Archieval Section Not for loan 2023-1613
Total holds: 0

Vapour compression refrigeration (VCR) system was designed, developed, and fabricated for testing alternative refrigerants such as R152a, R600a, R290 and mixture of R290/R600a (50/50% by mass) over presently used R134a with aluminium minichannel condenser. Heater bank was provided for controlling condensation and evaporator temperature along with sub-cooling and superheating temperature by using PID controllers. All the refrigerants are tested for condensation temperature ranging from 40°C to 55°C while evaporation temperature ranges from –15°C to 15°C. Refrigerant charge was reduced 50% with the minichannel condenser over the conventional condenser. Two phase condensation heat transfer coefficient correlation was developed from the experimental data points within ±15% with existing correlations.

There are no comments on this title.

to post a comment.

Click on an image to view it in the image viewer

Local cover image
Share
Unique Visitors hit counter Total Page Views free counter
Implemented and Maintained by AIKTC-KRRC (Central Library).
For any Suggestions/Query Contact to library or Email: librarian@aiktc.ac.in | Ph:+91 22 27481247
Website/OPAC best viewed in Mozilla Browser in 1366X768 Resolution.